Kidde Commercial GSA-CC1S Single Input (Riser) Module with Strobe Synchronization

GSA-CC1S is a single-input riser control module designed to switch one signaling or audio circuit in a compatible fire alarm system. It features a built-in ring-tone generator and strobe synchronization for coordinated notification.
Features:
- Provides UL 1971-compliant auto-sync output for visual
signals
Use for connecting a supervised output circuit to a supervised
24 Vdc riser input and synchronizing multiple notification appliance circuits.
- Functions as an audible signal riser selector
Use as a synch module or for connecting supervised 24 Vdc
Audible/Visible signal circuits, or 25 and 70 VRMS Audio
Evacuation and Telephone circuits to their power inputs.
- Built-in ring-tone generator
When configured for telephone circuits, the GSA-CC1S generates its own ring-tone signal, eliminating the need for a separate ring-tone circuit.
- Automatic device mapping
Signature modules transmit information to the loop controller
regarding their circuit locations with respect to other Signature
devices on the wire loop.
- Electronic addressing
Programmable addresses are downloaded from the loop controller, a PC, or the SIGA-PRO Signature Program/Service Tool;
there are no switches or dials to set.
- Intelligent device with microprocessor
All decisions are made at the module to allow lower communication speed with substantially improved control panel
response time and less sensitivity to line noise and loop wiring
properties; twisted or shielded wire is not required.